Fire FightingPumps
End suction, double suction, in-line and multistage fire pumps within the scope of NFPA 20, feeding sprinkler, fire hose cabinet, hydrant and other water-based fire fighting systems.

4 pump types, one duty
Technical data for each type, the selection table based on NFPA 20 rated capacities and the applications are given on each product page.
01End Suction Fire Pumps
End suction fire pumps are horizontal, single-stage centrifugal pumps with volute casing and closed impeller.
- Capacity
- 25 – 5000 GPM
- Head
- 40 – 100 m
- Discharge flange
- DN32 – DN250
- Casing pressure
- 10 – 16 bar
02Double Suction Fire Pumps
Double suction fire pumps have a wide capacity and head range, and allow easy maintenance and repair without dismantling the motor and pipework.
- Capacity
- 400 – 5000 GPM
- Head
- 50 – 140 m
- Discharge flange
- DN65 – DN200
- Casing pressure
- 16 – 25 bar
03In-Line Fire Pumps
In-line fire pumps are single-stage, close-coupled centrifugal pumps with a volute casing and a closed impeller; they can be installed directly in a straight pipe run.
- Capacity
- 25 – 1250 GPM
- Head
- 30 – 90 m
- Discharge flange
- DN40 – DN200
- Casing pressure
- 10 – 16 bar
04Horizontal Multistage Fire Pumps
Horizontal multistage fire pumps are centrifugal pumps with a radially split casing, closed impellers and diffusers.
- Capacity
- 25 – 2500 GPM
- Head
- 60 – 170 m
- Discharge flange
- DN32 – DN200
- Casing pressure
- 30 bar
Which pump, which motor?
Select the rated capacity and head; the corresponding pump size and motor power are listed for the four types.
Rated capacity (GPM)
Head (m)

Designed to NFPA 20 requirements
NFPA 20 – STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION
NFPA 20 is the globally recognised principal standard for the selection and installation of stationary fire pumps. This standard aims to ensure that pumps supplying water to sprinkler systems, fire hose cabinets, hydrant systems and other water-based fire fighting systems are correctly selected, safely installed and reliably deliver the expected capacity and pressure in the event of a fire. It covers stationary pumps used for fire protection, including horizontal and vertical centrifugal pumps, vertical turbine pumps and positive displacement pumps.
Performance characteristic · representative curve
Rated capacities (GPM)
According to NFPA 20, the rated capacity of a fire pump must be one of these values.
System features
- Starts automatically in the event of fire
- Meets the specified rated capacity and pressure values
- Standby, monitoring and control functions are defined
- Acceptance tests and periodic inspections are specified
Performance criteria
- At closed valve (zero flow), head is no more than 140% of the rated value
- At 150% of rated capacity, the head is not less than 65% of the rated value
- At rated capacity, the flow velocity in the suction pipe is less than 3 m/s

Designed to UL / FM requirements
FIRE PUMPS DESIGNED TO UL / FM REQUIREMENTS
The UL Listed and FM Approved marks indicate that fire pumps have been tested and certified by independent international organisations in accordance with the relevant standards. These marks assure the investor and the operator that their protection system has been tested to start in the event of fire and is internationally recognised. Fire pumps are designed to the requirements of these standards; listing and approval are granted separately by the relevant bodies for the manufacturer’s product.
UL / FM test criteria
- Meeting the specified capacity – pressure curve
- Continuous operation and durability
- Start-up and continuity of performance
Advantages
- Easier acceptance by insurance companies and regulatory bodies
- Documented performance supporting system design in compliance with NFPA 20
- Safety to international standards in high-risk facilities (industrial plants, power plants, large warehouses, shopping centres, etc.)
Design features in accordance with UL / FM
- The declared capacity may only be one of the standard rated capacities; above 5000 GPM it increases in 500 GPM steps
- All bolts, screws, etc. in contact with the pumped liquid are of bronze or corrosion-resistant material
- Supplied together with automatic air release valve, casing relief valve and pressure gauges
- Bearings with an L-10 life of at least 5000 hours at maximum load
- At least 4 rings of soft packing and a lantern ring (at least 5 rings if there is no lantern ring)
- Impeller, wear rings, shaft, lantern ring and glands made of corrosion-resistant material
Fire pump set: complete packaged system
Main pump, standby pump, jockey pump, control panels, manifolds and valves on a common base frame; ready to be tested as a system.

The fire pump set is a complete packaged system comprising the main pump, standby pump, jockey pump, panels, manifolds, valves, etc., all on a common base frame. Under Turkish fire regulations, a system with a single main pump must have a standby pump of the same capacity; where there are several main pumps, at least 50% of the total capacity must be backed up.
Start-up sequence
When the system pressure falls below the set value, the jockey pump starts first on a signal from the pressure switch. If the pressure continues to fall, the main pump starts; if the system pressure still cannot be maintained, the standby pump starts.
Where automatic stop is permitted by the applicable standard and the authority having jurisdiction, once the pressure has returned to normal the electric motor-driven pump is stopped after running for at least 10 minutes, and the diesel engine-driven pump after running for at least 30 minutes.
PSYSTEMNormal · system at pressure, pumps in automatic modePJSETPressure maintenance (jockey) pump startsP1SETMain pump (electric motor-driven) startsP2SETStandby pump (diesel engine-driven) startsSetting sequence: PSYSTEM > PJSET > P1SET > P2SET
All types, in a single table
| Pump type | Suction flange | Discharge flange | Capacity | Head | Speed | Operating temperature | Casing pressure |
|---|---|---|---|---|---|---|---|
| 01End Suction Fire Pumps | DN50 – DN300 | DN32 – DN250 | 25 – 5000 GPM | 40 – 100 m | up to 3000 rpm | -10 °C to +120 °C | 10 – 16 bar |
| 02Double Suction Fire Pumps | DN100 – DN250 | DN65 – DN200 | 400 – 5000 GPM | 50 – 140 m | up to 3000 rpm | -20 °C to +80 °C | 16 – 25 bar |
| 03In-Line Fire Pumps | DN40 – DN200 | DN40 – DN200 | 25 – 1250 GPM | 30 – 90 m | up to 3000 rpm | -10 °C to +110 °C | 10 – 16 bar |
| 04Horizontal Multistage Fire Pumps | DN40 – DN250 | DN32 – DN200 | 25 – 2500 GPM | 60 – 170 m | up to 3000 rpm | -10 °C to +140 °C | 30 bar |



